Main function
Soft starter
Product series / family name
PSE series
Network frequency
50/60 Hz
Functions
Soft-starter FieldBus Plug RUN Signal Kick start Torque control HMI for settings Cooling system Bow thruster Coated PCBA Fuse protection
Supply voltage (AC)
208Vac-600Vac 208Vac-600Vac (220Vac / 230Vac / 240Vac / 380Vac / 400Vac / 415Vac / 440Vac / 480Vac / 500Vac / 525Vac)
Rated current
143A (nom.; in-line) 106A (HD Heavy-Duty; in-line)
Rated active power (kW)
75kW (nom.; 400Vac; in-line) 40kW (nom.; 230Vac; in-line) 90kW (nom.; 500Vac; in-line) 30kW (HD Heavy-Duty; 230Vac; in-line) 55kW (HD Heavy-Duty; 400Vac; in-line) 75kW (HD Heavy-Duty; 500Vac; in-line)
Rated power (HP)
100HP (nom.; 440/480Vac; in-line) 50HP (nom.; 220/240Vac; in-line) 40HP (nom.; 200/208Vac; in-line) 125HP (nom.; 550/600Vac; in-line) 30HP (HD Heavy-Duty; 200/208Vac; in-line) 40HP (HD Heavy-Duty; 220/240Vac; in-line) 75HP (HD Heavy-Duty; 440/480Vac; in-line) 100HP (HD Heavy-Duty; 550/600Vac; in-line)
Rated insulation voltage (Ui)
600 V
Control Voltage (DC)
24Vdc
Protection functions
Locked rotor Current underload Current limit Electronic motor overload
Mounting mode
Surface / wall
Digital inputs
1 x digital input (Start) 1 x digital input (Stop) 1 x digital input (Reset)
Digital outputs
1 x digital output (K1; FAULT signal) 1 x digital output (K2; RUN) 1 x digital output (K3; bypass signal / TOR)
Analog outputs
1 x analog output (4-20mA)
Contacts type
SPDT (Single Pole Double Throw) (Fault signal)
Visual position indicator
LED indicators
Technical compatibility with
AF140 contactor
Power consumption
16 VA (Inrush) 31 VA
Power dissipation/losses
12.1 W
Application type
Small size pump applications Centrifugal pumps Compressors Conveyor belts (short) Elevators Escalators
Order code / Manufacturer SKU
PSE142-600-70
Manufacturer product status
Commercialized
Compliant with standard(s)
CE IEC 60947-1 EN 60947-4-2 CCC KC ANCE cULus UL 508 CSA C22.2 No 14 C-tick EAC
For connecting the PSR Soft Starters to the MS Motor Starters, this range covers motor currents from 3 to 105A. With their compact design, the PSR Soft Starters are ideal for installations in places where space is limited and where there is a demand for easy installation. All sizes include a run signal relay, while sizes from 25A are also provided with an output signal for TOR (Top of Ramp), i.e. Full Voltage. With standard performance the PSR Soft Starters handle 10 starts per hour. When an auxiliary fan is added, the starting capacity is increased to 20 starts per hour.
This range covers motor currents from 3 to 45A. With their compact design, the PSR Soft Starters are ideal for installations in places where space is limited and where there is a demand for easy installation. All sizes include a run signal relay, while sizes from 25A are also provided with an output signal for TOR (Top of Ramp), i.e. Full Voltage. With standard performance the PSR Soft Starters handle 10 starts per hour. When an auxiliary fan is added, the starting capacity is increased to 20 starts per hour.
Reduce the number of stops in your production by allowing your softstarter to do more than just starting. Our softstarters reduce the mechanical stress on your motor application, which will increase your uptime. Torque control, pump cleaning, motor brake and many other features enable you to operate your process at its full potential.